LAL 2.25 - Oil Burner Control 220V

Type: LAL 2.25

Application: Control and supervision of oil atomization burners

Flame detectors: QRB1..., QRC1..., or RAR...

Availability: In Stock

Condition: Lotted

Brand: Landis & Gyr

Origin: Germany

Price: Available on request

Note: Plug-in base needs to be ordered separately.

Use

- For the control and supervision of oil atomization burners

- For burners of medium to high capacity

- For intermittent operation (at least one controlled shutdown every 24 hours)

- Can be universally used with multistage or modulating burners

- Suited for use with stationary air heaters







General unit data

Mains voltage: AC 220 V -15 %...AC 240 V +10 %

Mains frequency: 50...60 Hz ±6 %

Primary fuse (external): max. 10 A (slow)

Weight: approx. 1000 g

Weight plug-in base: approx. 165 g

Power consumption: Approx. AC 3.5 VA

Mounting orientation: No restrictions

Temperature range (operation): -20...+60 °C

Humidity: < 95 % r.h.

If you have any questions about this product please email us at saadwaheed09@gmail.com