LFL1.635 - Burner Controller

Type: LFL1.635

Serie: 01

Application: Gas, oil, and dual fuel burners

Mains voltage: AC 220 V -15/+10 %

Pre-purge time: 66 seconds

Brand: Landis & Gyr

Condition: New

Stock: 1pc (subject to availability)

Price: Available on request

Plug-in base: Ordered separately

Burner Flame Safeguard Control

The LFL... is a compact electro-mechanical primary safeguard control designed to provide burner sequencing, automatic ignition and continuous flame monitoring for gas, oil, and dual fuel, single burner applications.

The LFL... is applicable for on-off, multi-stage or modulating burners. The LFL... is designed for direct main burner ignition, intermittent or interrupted pilot operation.

The LFL... integrates the flame amplifier, purge timer and sequencer in a single control. Flame supervision is accomplished using UV sensor or flame rod detection.






















General unit data

Mains voltage: AC 220 V -15/+10 %

Mains frequency: 50...60 Hz ±6 %

Internal fuse: 6.3 A (slow)

External fuse: Maximum 10 A (slow)

Weight: approx. 1000 g

Weight plug-in base: approx. 165 g

Power consumption: 3.5 VA

Mounting orientation: No restrictions

Temperature range: -20...+60 °C

Humidity: < 95 % r.h.

For more information on technical data, please see data sheet.