LAE1 - Oil Burner Controller

Type: LAE1

Reference code: 8846

Application: For supervision and control of oil burners

Mains voltage: 220 - 240 VAC

Adjustable safety time (TSA): 0...9 s (factory setting 2 s)

Adjustable prepurge time (t1): 8...63 s

Product category: Oil Burner Controllers (listed alphabetically)

Brand: Landis & Gyr

Condition: Used

Stock: 1 pc (subject to availability)

Price: Available on request

Note: Plug-in base needs to be ordered separately.

Product Location: Products > Oil Burner Controllers > LAE1 (listed alphabetically)

Oil Burner Controller - LAE1

Oil burner controller for use with burners of any capacity in intermittent operation. For safety reasons, at least one controlled shutdown must take place every 24 hours.

Use

The LAE1... with the associated flame detector RAR7 or RAR8 is used for the fully automatic startup and supervision of

– single-stage forced draft burners

– multistage forced draft burners

– modulating forced draft burners

– with any oil throughput

































General unit data

Mains voltage: AC 220 V -15 %...AC 240 V +10 %

Mains frequency: 50 Hz ±6 %

External primary fuse: 10 A (slow)

Power consumption: 6 VA (in operation)

Degree of protection: IP 40, must be ensured through mounting

Mounting position: optional

Weight: approx. 1.85 kg

Temperature range: -20...+60 °C

Humidity: < 95 % r.h.

For more information on technical data, please see data sheet.

























If you have any questions about this product please email us at saadwaheed09@gmail.com